G&D Chillers label showing R-1234ze, a low-GWP A2L refrigerant for data center chillers

Data Center Chiller Refrigerants Under EPA Rules: A2L, R-1234ze, R-513A, R-515B and R-290 (2026 Update)

November 9, 2026

By Paul Johnson, Technology & R&D, G&D Chillers

Short answer: Under the EPA's Technology Transitions rule, new data center and IT cooling equipment must use refrigerants with a global warming potential (GWP) of 700 or less starting January 1, 2027. That rules out R-134a (GWP 1,430) in new data center chillers, and points buyers to lower-GWP options such as R-513A, R-515B and the A2L refrigerant R-1234ze.

This guide explains the rule, compares the main chiller refrigerants, and shows which options G&D offers on its GDX Series data center chillers. It reflects EPA's sector tables as updated on August 28, 2026. This article is general information, not legal advice. Confirm requirements in 40 CFR Part 84, Subpart B.

What are the EPA refrigerant rules for data center chillers?

The EPA's Technology Transitions rule, issued under the AIM Act, sets a 700 GWP limit for the subsector "data centers, computer room air conditioning, and information technology equipment cooling," with a January 1, 2027 compliance date (EPA). The same limit and date apply to factory-built products and to field-installed systems.

Rule element Data center / IT cooling requirement Source
GWP limit 700 EPA sector tables
Manufacture and import of self-contained products (e.g., packaged chillers) January 1, 2027 EPA sector tables
Installation of new field-assembled systems January 1, 2027 EPA sector tables
Sale and distribution of non-compliant products Prohibited three years after the manufacture/import date EPA fact sheet
Existing equipment May keep operating and be serviced for its useful life EPA fact sheet

EPA's May 26, 2026 reconsideration rule extended deadlines for several sectors, including semiconductor process chillers and cold storage, but the data center subsector remains at 700 GWP from January 1, 2027. Comfort cooling chillers have had a 700 GWP limit since January 1, 2025.

Does the EPA rule affect existing data center chillers?

No. Existing chillers can keep running and be repaired with their current refrigerant for their full service life. The rule applies to new products and new system installations.

One caution: EPA treats some upgrades as a new installation. Increasing a system's cooling capacity is one example, so plant expansions should be planned with a compliant refrigerant (EPA fact sheet).

Which refrigerants can data center chillers use under the 700 GWP limit?

The table compares common chiller refrigerants. GWP values use the IPCC AR4 basis used by EPA under the AIM Act.

Refrigerant GWP (approx.) ASHRAE safety class Meets 700 GWP limit? Typical use in data center chillers
R-134a 1,430 A1 No Legacy centrifugal and screw chillers
R-513A ~630 A1 Yes Drop-in path from R-134a, non-flammable
R-515B ~300 A1 Yes Non-flammable, lower GWP than R-513A
R-1234ze(E) <1 A2L Yes Ultra-low GWP centrifugal chillers
R-514A ~2 B1 Yes Low-pressure centrifugal chillers
R-32 675 A2L Yes (just) Scroll and small packaged units
R-454B 466 A2L Yes Scroll and small packaged units
R-290 (propane) 3 A3 Yes Small packaged chillers with low charge limits

Chart showing refrigerant global warming potential (GWP) values compared with the 700 GWP limit

"Most operators we talk to want two things from a refrigerant: compliance that will not change again in five years, and no new safety classification in the mechanical yard. R-515B and R-513A give them A1 today, and R-1234ze gives them near-zero GWP if they are ready to design for A2L." — Paul Johnson, Technology & R&D, G&D Chillers

What is an A2L refrigerant, and is it safe for data centers?

An A2L refrigerant has low toxicity and lower flammability: it is hard to ignite and burns slowly if it does. R-1234ze, R-32 and R-454B are all A2L refrigerants.

A2L refrigerants are used safely in data center chillers every day, but they bring design requirements. ASHRAE Standard 15 and the product safety standard UL 60335-2-40 set rules for refrigerant detection, ventilation and charge limits, especially for indoor equipment and machinery rooms. Outdoor air-cooled chillers, such as the GDX Air, usually simplify these requirements because the refrigerant circuit stays outside the building.

Can R-290 (propane) be used in data center chillers?

R-290 has a GWP of about 3, but it is an A3, highly flammable refrigerant, so safety codes limit how much can be used in one circuit. That makes it practical for small packaged chillers and less practical for the multi-megawatt centrifugal plants used in most data centers.

For large data center loads, most operators choose A1 blends (R-513A, R-515B) or A2L R-1234ze with oil-free centrifugal compressors.

Which refrigerants do G&D data center chillers use?

G&D's GDX Air and GDX Free (GDX-Cool) chillers are offered with R-134a, R-1234ze, R-513A or R-515B, all with Danfoss Turbocor oil-free magnetic bearing compressors (GDX Air, GDX Free).

G&D refrigerant option Complies with 700 GWP data center limit from Jan 1, 2027 Safety class
R-1234ze Yes A2L
R-515B Yes A1
R-513A Yes A1
R-134a No, for new U.S. data center installations after the compliance date A1

How should you choose a refrigerant for a new data center chiller?

Work through these five questions with your engineer:

  1. When will the chiller be manufactured and installed? Anything installed from January 1, 2027 must meet 700 GWP.
  2. Is the chiller indoors or outdoors? Indoor A2L installations need more detection and ventilation design.
  3. Do you want the lowest GWP or an A1 classification? R-1234ze is lowest GWP; R-515B and R-513A are non-flammable.
  4. What are your corporate climate targets? Lower GWP reduces the emissions impact of any leak.
  5. Are state rules stricter? Some states, including California, have their own HFC regulations.

Frequently asked questions

When does the EPA 700 GWP limit apply to data center chillers? January 1, 2027, for both manufacture and import of self-contained products and installation of new systems in the data center and IT cooling subsector.

Is R-134a banned in data centers? Existing R-134a chillers can keep operating and be serviced. New data center chillers and systems covered by the rule cannot use R-134a from January 1, 2027, because its GWP of 1,430 exceeds 700.

Is R-513A compliant with the new EPA rules? Yes. R-513A has a GWP of about 630, under the 700 limit, and is non-flammable (A1).

What is the lowest-GWP refrigerant for centrifugal chillers? R-1234ze(E), with a GWP below 1, is the most common ultra-low GWP option for oil-free centrifugal chillers.

Did the 2026 EPA reconsideration change the data center deadline? No. The May 2026 rule changed deadlines for other subsectors, but the data center subsector remains at 700 GWP from January 1, 2027.


Specify a compliant chiller. See G&D's low-GWP data center platforms and ask an engineer which refrigerant fits your site.